Line Voltage Regulator for Distribution Network

Line Voltage Regulator for Distribution Network

Page view
编号:
分类
Products
梗概
The line voltage regulator for distribution network is an intelligent compensation type AC voltage regulator. It is connected to the grid system in series to monitor the circuit voltage in real time,
时间
2018/07/31 16:06
I want to inquire price
产品描述
技术参数

Line Voltage Regulator for Distribution Network

 

Product Introduction

The line voltage regulator for distribution network is an intelligent compensation type AC voltage regulator. It is connected to the grid system in series to monitor the circuit voltage in real time, and ensure the stability and safety of electricity for the residents by adjusting the circuit voltage.  

■ Product Performance

 It adopts the solid-state grading voltage regulation mode, the terminal voltage can be raised and lowered, and the voltage is stable; ● The voltage regulation range is wide, and the voltage can be customized according to the application places; ● The state can be switched without harmonic distortion, and the sampling accuracy is high; ● The state can be switched smoothly, without significant voltage drop or obvious current impact; ● The individual phase regulation can be achieved with high degree of freedom; ● The modular design is applied in each phase of the device for easy maintenance; ● The equipment enjoys high voltage regulation efficiency and low loss, which will be in bypass mode when no voltage regulation; ● It is equipped with over-current protection device inside, which can ensure the safety of the device and the stability of the circuit when the faults such as short circuit or over current occur.     For example: INPLVR 30/0.23-1,refer to the single-phase pressure regulator with 30kVA capacity and 230V voltage  

■ Application

It is uneconomical to increase the distribution transformer or replace the circuit for the case where the terminal voltage exceeds the limit, the users' lines are installed on one meter box and the voltage fluctuation is large. Especially for the places featured with scattered user, large load changes, and long power lines in the rural, it is widely welcomed for high performance with lowest cost. Compared with increasing the distribution transformer or replace the power supply line, it is more economical to install a voltage stabilizing device at the end of the power supply line or in the line to stabilize the circuit voltage or qualify the terminal voltage. In addition, its construction period is short and it is easy to be implemented.  

■ Product Capacity

 
Product name Capacity (kVA) Number of phases Cabinet dimension (width * depth * height)
Line Voltage Regulator for Distribution Network 10kVA Simple phase 450*300*700
20kVA Simple phase
30kVA Simple phase
40kVA Simple phase
Line Voltage Regulator for Distribution Network 30kVA Three phases  
60kVA Three phases 700*450*1000
90kVA Three phases  
120kVA Three phases  
  Note: Other specifications can be customized.    

■ Principle of line voltage regulator

The line voltage regulator for distribution network is an intelligent compensation type AC voltage regulator. And it is mainly composed of the compensation circuit, voltage regulating circuit, a control circuit, input sampling circuit, output sampling circuit, output control circuit, protection circuit, and bypass circuit, etc. It can achieve the smooth switching of different states by the auxiliary switching circuit, without significant voltage drop and current overshoot. At any time, the device keeps the flow channel of the transformer winding current in existence, and effectively suppresses the possible magnetizing inrush current during the state switching. The whole device is simple in structure, and convenient to use; in addition, it is safe and reliable.    

■ Installation of the product

  Installation diagram of three-phase LVR device

Technical specification

 

Product specification

 
Applicable scope Rated working voltage Single phase: AC220V    Three phases: AC380V
Rated working frequency 50Hz (45Hz〜55Hz)
Applicable circuit Three-phase or single-phase circuit
Equipment capacity Single phase: 10-40kVA    Three phases: 30-120kVA
Regulation range and accuracy Regulation accuracy ±5%
调节时间
Regulation time
<0.3S
Voltage loss time 0S (no voltage loss time)
Voltage regulation range 20% for soil, and 10% for soil (Others can be customized)
Protection mode Temperature protection When the temperature of the device exceeds the setting temperature, the device will automatically switch to the bypass state.  When the temperature is lower than the threshold, it will switch back to the automatic voltage regulation state.
Over-voltage protection When the output voltage exceeds the setting voltage, the device will automatically switch to the bypass state, and then switch back to the automatic voltage regulation state after the voltage is within the setting value.
Over-current protection When the output current exceeds the setting current, the device will automatically switch to the bypass state, and then switch back to the automatic voltage regulation state after the current is within the setting value.
Lightning protection The lightning arrester is adopted to achieve the lightning surge protection
Working characteristics Efficiency Under full-load voltage regulation, it is more than or equal to 99%, while under bypass state, it is more than or equal to 99.8%
Work mode Automatic buck-boost mode, and bypass mode
Control mode Track the output voltage, and dynamically regulate the compensation voltage
Communication mode GPRS communication or WIFI communication (Others can be customized)
Working environment Working temperature -25 °C ~+60°C
Storage temperature -40°C 〜+85°C
Altitude Less than or equal to 2000 meters (for high altitude, it can be customized)
Relative humidity of the surrounding environment 5%-95% (without condensation)
Mechanical properties Noise ≤45db
Protective level IP44
Cooling mode 自然冷却
Natural cooling
Insulation resistance The input and output insulation resistance to ground is more than or equal to 5MΩ
Insulation strength Withstand input and output AC voltage to ground is 2000V/1 min, without flashover or breakdown
 